Commissioning
5.5 First commissioning with the AOP30
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
175
Note
When motor identification is complete, press the OFF key to cancel the power-on inhibit.
DANGER
When the rotating measurement is selected, the drive triggers movements in the motor that
can reach the maximum motor speed. The emergency STOP functions must be fully
operational during commissioning. To protect the machines and personnel, the relevant
safety regulations must be observed.
Note
If a fault is present when the stationary or rotary measurement is selected, motor
identification cannot be carried out.
Before rectifying the fault, you have to choose "No identification" and close the screen.
Motor identification can then be selected again via <MENU> - <Commissioning/service> -
<Drive commissioning> - <Motor identification>.