Electrical installation
4.6 Power connections
Drive converter cabinet units
60 Operating Instructions, 10/2008, A5E00288214A
4.6.5 Removing the connection bracket for the interference-suppression capacitor with
operation from an ungrounded supply
If the cabinet unit is operated from an ungrounded supply/IT system, the connection bracket
for the interference-suppression capacitor of the active interface modules (-A2) must be
removed.
8QVFUHZWKHVFUHZV07RU[7DQGUHPRYHWKHFRQQHFWLRQEUDFNHW
Figure 4-4 Removing the connection bracket for the interference-suppression capacitor
WARNING
Failing to remove the connection bracket for the interference-suppression capacitor on a
non-grounded system/IT system can cause significant damage to the cabinet unit.