Velocity Edge GX440 Istruzioni per gli Interventi Pagina 176

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 530
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 175
Commissioning
5.6 Status after commissioning
Drive converter cabinet units
176 Operating Instructions, 10/2008, A5E00288214A
5.6 Status after commissioning
LOCAL mode (control via operator panel)
You switch to LOCAL mode by pressing the "LOCAL/REMOTE" key.
Control (ON/OFF) is carried out via the "ON" and "OFF" keys.
You specify the setpoint using the "increase" and "decrease" keys or by entering the
appropriate numbers using the numeric keypad.
Analog outputs
The actual speed (r0063) is output as a current output in the range 0 to 20 mA at analog
output 0 (X522:2 and 3).
A current of 20 mA is equal to the maximum speed in p1082.
The actual current value (r0068) is output as a current output in the range 0 to 20 mA at
analog output 1 (X522:5 and 6).
A current of 20 mA corresponds to the current limit (p0640), which is set to 1.5 x the rated
motor current (p0305).
Digital outputs
The "enable pulses" signal is output at digital output 0 (X542:2 and 3).
The “no fault active” signal is output at digital output 1 (X542:5 and 6) (fail safe).
The "ready to start" signal is output at digital output 8 (X541:2).
Vedere la pagina 175
1 2 ... 171 172 173 174 175 176 177 178 179 180 181 ... 529 530

Commenti su questo manuale

Nessun commento